Skip to main content

Basic Design Considerations for a Laboratory

The Ministry of Health & Family Welfare, under the Drugs & Cosmetics Act, laid down “Good Laboratory Practices” requirements and made the compliance of GLP mandatory from 1st November 2010, for all pharma companies. Close to the requirement of Indian Law; WHO has also come out with a draft guidance document of GLP for all establishments engaged in testing of pharmaceutical products. Further for last few years, it is also noticed that laboratory’s functioning, its design, layout, aesthetic appearance and adequacy of work area have been one of the major areas where various regulatory officials have been spending time and making observations for compliance. The above two publications have raised a furor in the industry to retrofit the existing facilities as well those upcoming ones to now focuson making their upcoming set-up’s GLP/GMP compliant.

Lab Classification

Broadly speaking laboratories can be classified as wet or dry labs. Wet labs use chemicals for reactions and dry labs where instrumentation and very small amounts of chemicals are used in testing.
Wet labs require chemical resistant work surfaces and cabinets that are liquid tight to contain spillage. Chemical and glassware storage and fume hoods are significant factors in space planning and furniture selection.
Dry analytical labs typically require a lot of large shelving to support instrumentation. Height-adjustable work surfaces may be required to allow large counter-mounted equipment to be placed at a comfortable operating height or be completely removed to provide instant space for the addition of floor mounted equipment.

The wet and dry categories are not without crossover. Wet labs will always have some instrumentation and dry labs usually will have limited chemicals on hand. Some laboratories may contain both wet and dry areas.

Lab Planning Concepts

The laboratory module is the key unit in any lab facility. A well thought of and the well designed module will primarily have flexibility and expansion as its two most important benefits. The other criterions are functionality, safety, interaction, aesthetics and cost-effectiveness.

However, first and foremost it is absolutely critical to identify the lab and non-lab areas at the initial planning stage. Zoning the premises or the building between lab and non-lab spaces reduces the project capital and operational costs. Labs require 100% outside air while non-lab spaces function moreover on the principal of recirculated air similar to commercial buildings. Next step is to establish the interrelationship between a lab and other functional labs, administrative and lab support areas, break areas, the main traffic corridor and service and utility corridors. There is a number of ways to plan and organize these spaces.

Circulation

A single corridor with multiple options is the most adopted one.

A single corridor lab design with labs & offices adjacent to each other

single corridor design

The shaded area in the above layout shows the working areas-cubicles and cabins of the research scientists attached to the labs.

A single corridor with office clustered at the end or in the middle.

single corridor with office clustered

The shaded area in the above layout shows the lab area segregated physically from non-lab areas. The non- lab areas are located near the entrance of the facility.

A single corridor with office clusters directly accessing the main labs

single corridor with office cluster

The shaded area in the adjoining layout shows the placement of scientists’ work tables next to the individual lab.

For a medium size lab, option 2 with office clusters at the end or in the middle works the best. This layout segregates lab and non-lab spaces thereby differentiating between the mechanical requirements and resulting in cost effective lab operating solution.
The other way to go about for lab designing is by deciding whether to have a single main corridor with a view from labs to the exterior or to have labs located in the interior and use the wall length for main traffic and utility corridors. Both the options

have pros and cons. Labs planned along the external wall allow natural light to flow in and easy extraction of toxic air. Certain special instruments and equipments such as nuclear magnetic resonance apparatus (NMR), electron microscopes and lasers have to be placed in low light areas or area with no natural light and hence have to be located in the interior of the building.

Research scientists many times prefer detaching the ‘hot zone’ from the main lab area. This is the space where equipments emit hot air (ovens) or fume hoods etc and large amount of toxic air is exhausted. This area doesn’t need to be air conditioned and it reduces considerable load from HVAC system. A proper exhaust layout supported by forced draft fresh air ventilation is sufficient. This area is moreover like a dead space where the research scientists set up the assembly and visit the zone only for the purpose of monitoring. The other point of view here is, since this area is not so habitable, the finishing elements like false ceiling or epoxy flooring can be avoided further cutting the costs. Looking at the above advantages, it is advisable to adopt this practice for a medium size lab.

lab area

Open labs:

In open labs, researchers share not only the space itself but also equipment, bench space, and support staff. The open lab format facilitates

communication between scientists and makes the lab more easily adaptable for future needs. It can be adopted by deciding a grid of lab operations which is normally in two directions. The horizontal plane caters to the human movement and the physical expansion of lab while the vertical plane caters to the drop down points for mechanical, electrical, plumbing and utility systems. This pattern gives the flexibility and avoids the interception between the human and mechanical interface.

Lab Layout

The layout of a lab can have any shape or form. It can be linear, square, rectangular or curvilinear. Typically a lab has a width varying from 10’-0” to 20’-0” and depth which may vary from 20’-0” to 30’-0”. The depth depends upon the individual requirement of a laboratory.

The width criteria is based on two rows of equipment and lab tables of 2’-6” depth along each wall and a 5’-0” aisle in the centre for movement. If it’s a 20’-0” wide lab, then it has 2 aisles running parallel to the longitudinal walls with a 5’-0” wide island table in the centre thereby providing for maximum worktops and assemblies to take place. In either case it is mandatory to have at least 5’-0” aisle for safe and easy movement and operations.

Lab Aesthetics & Finishes

Once the basic lab boundary is set, planning for lab interiors and finishes has to be taken up. Flooring, ceiling and walls are the static elements of lab interiors. Laboratories should be free from air pollution, cross-contamination and zero tolerance for insects and rodents. Research activities by nature produce toxic elements in the air. So it is important that all the interior surfaces are smooth, free from cracks and permit easy cleaning and disinfection. Treating the walls and floor with epoxy coating ensures a smooth and homogeneous surface. However, it can prove to be an expensive solution for a medium size lab in which case the floor can be treated with joint free vitrified tiles which are not only easy to maintain but are cost effective as well.

The walls can be treated with a minimum thickness of epoxy coating or can be finished with regular washable lustre paint with low VOC. The other option to walls is to have glazed aluminium anodized partitions interconnecting the labs. This has an added advantage. It creates openness in the entire facility, establishes visual connection between the labs and enables the transmission of light. These partitions also give flexibility in terms of reconfiguration and expansion of lab layout for futuristic needs.

A grid of 2’x2’ modular false ceiling above the service carriers gives a finished look to the lab. The biggest advantage of the modular ceiling is that it controls the volume of lab thereby reducing the HVAC load and cost. In addition, this pattern provides the flexibility of adding, shifting, and relocation of supply and exhaust ducts as and when new equipment or fume hoods are added or eliminated.

Few points that can be easily taken care of:

  • Eliminate cross-contamination between laboratories
  • Minimize areas requiring controlled environments
  • The laboratory doors should be automatically self-closing. Such self-closing
    doors are to be able to be opened with a minimum of effort so as to allow easy
    access and outlet for everyone
  • Consider cascading supply air from non-laboratory spaces to laboratory
    spaces for exhaust
  • Spaces between benches, cabinets, and equipment must be accessible for
    cleaning and allow for servicing of equipment.
  • Each laboratory must contain a sink. Laboratory sinks should have lips that
    protect sink drains from spills. Waste water lines should be separate from
    domestic sewage
  • Chemical storage shelves should not be placed above laboratory sinks.
    Separate ventilated chemical storage cabinets should be utilized supported by
    a proper exhaust system
  • Space allocation for gas cylinders at the same level but segregated from lab
    areas and supported by gas detection system. This will reduce the piping
    length.
  • Auxiliary valves for gas and vacuum lines should be located outside the lab.
  • Flexible connections should be used for connecting gas and other plumbed utilities. A shutoff valve should be located within sight of the connection and clearly marked
  • The entire facility should have fire safety provisions with a consideration of integrating the same with HVAC system
  • Non-lab area should have a provision for changing room at the entrance so that the chemists enter the lab only after wearing the overcoat and eye protection spectacles
  • The ancillary areas such as stability rooms with incubators or sample receiving areas or lab specific requirements in case of microbiology labs should be planned for in advance
  • Place fume hoods at “dead-end” locations away from entryways and circulation routes

Apart from the civil interior, the laboratories should be provided with adequate lighting and ventilation. The air ventilation system should provide dust free environment. Temperature should be between 23 to 27 degree C and humidity should be not more than 65%.

Finally, lab buildings start getting modified almost from the day they are occupied. Thus an early on design process has to be adopted. The purpose of the laboratory for which it is being built has to be clearly defined and there should be maximum if not equal amount of interaction and involvement between the stakeholders, the design team and the end users. It has to be understood that the designing of a layout is very user & requirement specific and should incorporate the current as well as the futuristic needs of the lab. Careful assessment of user’s needs and equipment requirements should be noted down. A good design will result into a synergism of greater productivity & better performance, informal interaction, team work, innovation and good working environment.

References:

  • http://www.wbdg.org/
  • http://www.labdesignnews.com/
  • http://indiaglp.gov.in/

Courtesy Archana Salil, Director and Principal Architect- Arena Consultants